| [打印] |
No.
Symbol
Initial初始
Setting设置
Purpose and Range
Group 1: General OCSS常规设置
1-1
RCB-NO
1
Car Identifier
轿厢标识
1 to 8 = car A to H
Car identifier in group.在
群控中的轿厢标识(序号)
1-2
EN-CON
0
Enable Contract Software合同软件授权
0 = disable contract software禁止
1 = enable contract software激活
Determines if the contract software, contained in the contract EPROM chips, should be executed.
1-3
EN-EMO
0
Enable Overlay Controller Functionality(启用覆盖控制柜功能性)
0 = disable overlay controller functionality
1 = enable overlay controller functionality
This parameter should be enabled when the OCSS resides on an EMO or TEMO.
Once a full MOD controller is in place; for example, an E411M or E311M controller, this parameter should be disabled.(到OCSS处于EMO或者TEMO时,应将此参数置一。一个完整的MOD控制柜使用时,比如,一个E411M或者E311M的控制柜时,此参数应该被取消)
1-4
SVT-PO
1
Service Tool Position Offset服务器位置偏移
0 = service tool positions start at landing 0(服务器位置从楼层0开始)
1 = service tool positions start at landing 1(从楼层1开始)
Specifies whether positions are displayed on the Service Tool starting at landing 0 or landing 1.(指定服务器上的位置显示是以1还是以0开始)
1-5
#RINGS
1
Number Of Rings Used For Communication
1 = Use one ring for most communication to save CPU使用一个环形通讯
2 = Use two rings for all communication使用二个环形通讯
This variable specifies the number of rings to be used by the OCSS to communicate with each other.(此变量指定OCSS用来彼此通讯的环数)
1-6
R-BAUD
192
Ring Communications Baud Rate环行通讯比特率
96 = 9600 baud
192 = 19200 baud
Defines baud rate used for ring communications.
Note that all the cars in the group must have the same ring communications baud rate.
Also note that the controller power must be cycled for the change to take affect.(定义环行通讯的比特率。注意:群组中所有的轿厢必须拥有同样的比特率。同时,要使改变生效,控制柜电源必须生效)
#p##e#1-7
EMS-O
PL******
00000000
EMS Options (EMS选项)
P bit = 0: disable EMS parameter passing(禁止EMS参数通过)
P bit = 1: enable EMS parameter passing(使EMS参数通过)
L bit = 0: transmit OCSS load states using ICD 4.1 or lower(用ICD4.1或者更低的版本传输OCSS负载状态)
L bit = 1: transmit OCSS load states using ICD 4.2 or higher(用ICD4.2或者更高的版本传输OCSS负载状态)
Systems with EMS v2.0 or lower must have parameter passing disabled.
Systems with an EMS configured as ICD 4.1 or lower must have the L bit set to 0.(EMS v2.0或者更低版本的系统必须禁止参数通过,配置ICD 4.1或者更低版本的EMS的系统必须使L位设定为0)
1-8
RSLCFG
0
RSL Configuration for E335M(E335M的RSL配置)
0 =
Car I/O read from car link, Hall I/O read from hall link, Group I/O read from group link.
1 =
Car I/O read from car link, Hall I/O read from car link, Group I/O read from group link.
2 =
Car I/O read from car link, Hall I/O read from car link, Group I/O read from car link.
3 =
Car I/O read from car link, Hall I/O read from hall link, Group I/O read from car link.
定义: 由E335M系统形成何种环行通讯链
Defines how the RSL links are configured for E335M systems.
1-9
SB-DLY
30
Stuck Button Processing Delay按钮延迟处理
0 to 255= process a stuck button every 0 to 255 seconds
Processes a stuck button periodically, so that the button will be serviced occasionally.(周期性地处理一个按纽,使它被经常性地操作)
1-10
CB-TYP
0
Car Button Type轿厢按钮类型
0 = default缺省、默认
#p##e#1 = mechanical机械的
2 = touch tube电子触摸
Defines the type of car button mechanism.(定义轿厢按纽机械类型)
1-11
HB-TYP
0
Hall Button Type大厅按钮类型
0 = default
1 = mechanical
2 = touch tube
Defines the type of hall button mechanism.(定义大厅按纽机械类型)
1-12
CPU-T
10
Free CPU Time Reading Interval
CPU读取时间间隔
1 to 255 = 1 to 255 seconds
Defines the interval over which minimum free CPU measurements are taken.
This is for engineering use only - do not change.(定义测量空闲CPU的最小间隔,这仅作为工程使用,不要改变)
1-13
FIELD1
0
Field Engineering Spare 1(现场工程备用功能1)
Reserved for Field Engineering patches.
Please report all patches to OECF, so that Software Configuration Management can be maintained.
1-14
FIELD2
0
Field Engineering Spare 2
Reserved for Field Engineering patches.
Please report all patches to OECF, so that Software Configuration Management integrity can be maintained.
1-15
#p##e#FIELD3
0
Field Engineering Spare 3
Reserved for Field Engineering patches.
Please report all patches to OECF, so that Software Configuration Management integrity can be maintained.
1-16
FIELD4
0
Field Engineering Spare 4
Reserved for Field Engineering patches.
Please report all patches to OECF, so that Software Configuration Management integrity can be maintained.
1-17
FIELD5
0
Field Engineering Spare 5
Reserved for Field Engineering patches.
Please report all patches to OECF, so that Software Configuration Management integrity can be maintained.
1-18
FIELD6
0
Field Engineering Spare 6
Reserved for Field Engineering patches.
Please report all patches to OECF, so that Software Configuration Management integrity can be maintained.
1-19
FIELD7
0
Field Engineering Spare 7
10 - Prevents car button I/O modules from flashing.
Reserved for Field Engineering patches.
Please report all patches to OECF, so that Software Configuration Management integrity can be maintained.