OTIS 3100R2控制系统调试资料
作者: 2009-05-15 14:25:59 浏览:209
[打印]

  1. 检查变频器中STARTUP菜单中的参数,如与现场情况不符应进行正确设置。

  2. 执行自学习操作,如果是无齿轮主机还应进行编码器定位。

  3. 确认以下变频器中参数:

  TRAVEL菜单

  中 Ramp out enable = Disable

  Speed ref 1 src = An inp 1 out

  Speed ref inv src = Down cont mon

  IO CONFIG菜单中 An inp 1 type = -10V…+10V

  DO 1 src = Door open mon

  DO 3 src = Brake open mon

  4. 如发现上述参数有误,则应进行以下操作:

  a) 导入1.0m/s的IO等配置参数(STARTUP/Import recipe,执行User 5);

  b) 按照3设置相应参数;

  c) 设置以下参数:

  Landing control = Disable

  Mlt spd s 0 src = NULL

  Mlt spd s 1 src = NULL

  Pre-torque src = Int pretorque

  Brake feedback/BRK feedback src = DI 4 monitor

  d) Save Config

  5. 用服务器检查LCBII是否已设置成LSVF_W模式:

  M1-3-1-4 Drive type = 17

  M1-3-1-6 DZ type = 1

  6. 确认并设置AMCB1板中以下参数:

  F7 Floor Number = 楼层数

  F8 Rated Speed = 变频器中Mechanical/Full scale speed*

  F9 Encoder Pulses = 变频器中Encoder config/Std enc pulses

  F10 Motor Rated RPM =变频器中Speed profile/Max liner speed*

  F24 Run Enable = 0

  *电机额定转速和电梯合同速度说明

  采用速度模拟量控制后,变频器中的Speed Profile菜单和Ramp Profile菜单中的数据不被变频器引用,其加减速和速度由AMCB1板给出(F1~F11)。

  当电机额定转速并不对应于电梯的合同速度时(如1.75m/s的主机用于1.5m/s的电梯),应根据电梯合同速度、曳引比、齿轮比和曳引轮直径计算出对应的电机转速,将该转速设置到变频器STARTUP/…/Mechanical/Full scale speed中,并监控Speed Profile /Max liner speed是否为电梯的合同速度